HVAC Meter PCE-LCT 1-ICA incl. ISO Calibration Certificate

Product Code:
PCE-LCT 1-ICA
Availability:
In Stock
Delivery Time
2–3 Business Days

Need Technical Support?

Our engineers are available to help you select the right module for your application.

Description

Description

HVAC Meter incl. ISO Calibration Certificate
For checking the leakage current / RMS Current measurement / Continuity and resistance test / Voltage measurement up to 400V

With the HVAC Meter, it is possible to measure leakage currents in the range of up to 100A. Leakage occurs when a current flows through an electrical conductor that is not normally designed to conduct electricity. The HVAC Meter captures these currents and displays them on the display. For example, the HVAC Meter can be used to detect insulation faults. This is particularly advantageous where machines are operated that cannot or must not be switched off and in which an examination of the insulation is pending. The fact that not only leakage currents can be measured with the leakage HVAC Meter, but also the normal current flow, voltage up to 400V, resistance and passage, the leakage HVAC Meter is ideal for the electrician, who has to perform other measuring tasks in addition to the device tests. Thanks to its compact design, the leakage HVAC Meter fits into any pocket. The robust rubber protection protects the measuring device against small drops from low heights and makes the leakage HVAC Meter a reliable companion especially in the field of electrical inspection and workshop technology.

Highlights

- Leakage current measurement via current clamp
- Current measurement up to 100 A
- Voltage measurement up to 400 V
- Continuity test
- Resistance measurement up to 400 Ω
- Digital 40-digit bargraph
- High resolution
- Maximum / minimum value retention in display
- Robust rubber protection
- Test leads included in delivery
- Incl. ISO Calibration Certificate

Specification

Leakage current and current (AC A)
Measurement ranges        ResolutionAccuracy
50 / 60 Hz400 Hz ... 1 kHz
40-mA10 µA± (1% + 0.5-mA)± (4.5% + 0.5-mA)
400-mA100 µA± (3% + 5-mA)± (3% + 5-mA)
4 A1-mA± (4% + 0.1-mA)± (4% + 0.1 A)
40 A10-mA± (4% + 1 A)± (4% + 1 A)
80 A10-mA± (2.5% + 1 A)± (3% + 1 A)
80 A - 100 A100-mA± (5% + 1 A)± (5% + 1 A)
Voltage (AC V)
Measurement rangesResolutionAccuracy
50 / 60 Hz400 Hz ... 1 kHz
400V1V± (1.5 % + 2 digits)± (2 % + 4 digits)
Resistance
Measurement rangesResolution
AccuracyAlarm
400 Ω0.1 Ω± (1% + 2 digits)Measurement value <38Ω
General Technical Specifications
Display3 3/4
Measured electrical propertiesAC V, AC A, resistance
Security standardsCAT III 300V / CAT II 600V
Diameter of the clip30 mm
Input impedance10 MΩ
Registration rate2 Hz (numerical values), 20 Hz (bar graph)
Operating temperature-10 ... 50ºC / 14 ... 122ºF
Operating humidity<85% H.r.
Storing temperature-20 ... 60ºC / -4 ... 140ºF
Auto shut-offAfter 30 minutes
Power9 V battery
Input current10-mA
Weight200 g / < 1 lb
Dimensions210 x 62 x 35.6 mm / 8.2 x 2.4 x 1.4 in