HVAC Meter / HVACR Tester PCE-PME 4

Product Code:
PCE-PME 4
Availability:
In Stock
Delivery Time
2–3 Business Days

Need Technical Support?

Our engineers are available to help you select the right module for your application.

Description

Description

HVAC Meter / HVACR Tester up to ±4 kPa / 13 selectable units / data logging and USB-C interface / PC software / export to xls file

The digital HVAC Meter / HVACR Tester is an accurate and compact meter for differential pressure measurement in a wide range of applications, such as measuring filter resistances, pressure in furnaces, orifices, gas-air ratio equalisation, combustion processes, air conditioning systems, ventilation systems, etc. The HVAC Meter / HVACR Tester is suitable for measuring non-aggressive and non-explosive gases.

The HVAC Meter / HVACR Tester offers a variety of measuring functions such as maximum, minimum and average value calculation and a HOLD function. It offers an integrated data logging function with adjustable logging interval and real-time communication with a PC as well as export of the logged data as an xls file. The rechargeable battery enables an operating time of approx. 13 hours. The HVAC Meter / HVACR Tester has an audible alarm for monitoring during use. With 13 selectable pressure units, it can be flexibly adapted to individual requirements.


Highlights

- MAX, MIN, AVG value, HOLD
- audible alarm
- 13 selectable pressure units
- data logging and software
- rechargeable lithium battery
- LC colour display
- date and time display

Specification

Differential pressure 
Measurement range up to  -4 ... +4 kPa
Resolution  0,01 kPa
Accuracy  ±1 % FS
  
Differential pressure 
Measurement range up to  -40 ... +40 mbar
Resolution  0,1 mbar
Accuracy  ±1 % FS
  
General technical data 
Measuring functions  MIN, MAX, HOLD, AVG
Units  inHg, Pa, bar, mmHg, mbar, hPa, inH₂O, kPa, psi, kg/cm², psi, Ozf/in², ftH₂O
Display type  LC colour display
Storage medium  Internal memory
Storage capacity  15996 Measurements
Storage interval from  1 s
Storage interval to  9999 s
Interface  USB-C
Operating time  13 h
Automatic power-off from...to  1 ... 99 min.
Automatic power-off can be deactivated  Yes
Alarm  Acoustic
Alarm modes  Above, below
Overpressure  3 kPa
Menu language  English
Protection class (device)  IP20
Power supply  5 V
Weight  180 g
Operating conditions  -10 ... 60 °C , 0 ... 95 % RH
Storage conditions  -10 ... 60 °C , 0 ... 95 % RH
Capacity  1000 mAh
Dimensions ( W x H x D )  63 x 162 x 32 mm